Range 11.B - Multirisk Cabinets - EN 14470-1 Type 90,60,30,15 Minutes
CONFORMITY
- "Flammable" compartment tested and approved according to EN 14470-1 (04/2004) norm.
- Large warning labels in compliance with ISO 3864, 92/58/CEE European directive, EN 14470-1 (04/2004), and NF X08.003 norm.
ADVANTAGES
- Allows segregated storage per product famillies.
- Fire resistance tested and approved by an independent European laboratory.
- "Corrosive" compartments built in Cellular PVC, offering high chemical corrosion resistance.
SPECIFICATION
- Storage in 4 separate compartments with ventilation (Ø100) centralized on the cabinet roof (for possible connection).
"Flammable" compartment EN 14770-1
- Double wall construction: outer housing made of sheet steel; inner body made of H.P.L (High pressure laminated) coated sheet.
- Thermal insulation panel between the walls avoiding thermal bridges.
- White epoxy paint RAL 9010.
- "Flammable" and "No open flame" large warning labels.
- Static ground connection.
- Opening vents with outlet Ø 100 mm for possible external connexion.
- In case of fire a thermo-fuse automatically seals off the ventilation system.
- Thermo-expanding seals off the door allow keeping the internal body fireproof.
- Self-locking door with cylinder lock.
- Key-locking system.
- Possibility to keep the door open. If the temperature rises to 50°C, a fuse link closes the door automatically.
- 3 adjustable retention shelves.
- Removable retention tank on the bottom.
"Toxic" compartment
- Built in white Cellular PVC.
- "Toxic" large warning label.
- High and low vent.
- Handling glazed door with key-locking system.
- 1 retention sliding drawer.
"Bases" compartment
- Built in white Cellular PVC.
- "Bases" large warning label.
- High and low vent.
- Handling glazed door with key-locking system.
- 1 retention sliding drawer.
"Acid" compartment
- Built in white Cellular PVC.
- "Acid" large warning label.
- High and low vent.
- Handling glazed door with key-locking.
- 3 retention sliding drawers.
Each compartment is divided in major and one (or two) secondary compartment (H 420 x W 110 x D 540 mm). The second
one may be used for empty bottles storage. See table.
OPTIONS
- Additional shelves (model: E8A2 and E794).
- Perforated cover plate (model: C794).
Model |
Fire resistance (minutes) |
External Dim. H x W x D (mm) |
Weight (kg) |
Major compartments details |
Number of secondary compartment |
Description |
Internals dim. HxWxD (mm) |
Storage capacity (L) |
Retention capacity (L) |
Number of retention shelves/tanks |
MR9 |
90 |
1950x1270x615 |
395 |
Flammable |
1620x490x410 |
105 L |
38 |
4 |
0 |
MR6 |
60 |
390 |
Acids |
870x467x540 |
102 kg |
42 |
3 |
2 |
MR3 |
30 |
385 |
Bases |
420x467x540 |
34 kg |
14 |
1 |
1 |
MR1 |
15 |
380 |
Toxic |
420x467x540 |
34 kg |
14 |
1 |
1 |
E794 |
- |
30x490x410 |
3 |
Additional
shelf for "flammable" compartement |
C794 |
- |
90x480x400 |
4 |
Perforated
cover plate to put in retention tank for "flammable"
compartment |
E8A2 |
- |
84x457x482 |
6 |
Additional
sliding drawer for major "Acid"/"Base"/"Toxic"
compartements |
B8A |
- |
50x110x530 |
1 |
Additional
tank for secondary compartments (acids, bases,
toxic) |
The manufacturer keeps the right to modify technical characteristics without notice. Edition 03/2009.